No water in the rooms? What to check first
Short answer. In a hotel that stores its own water, a guest with no water almost always means the tank or pump that feeds the rooms has stopped, not that the city supply is off. Check in this order: the tank that feeds the rooms, then whether the transfer or booster pump is running and its breaker is on, then the cistern, then valves and airlocks. The lasting fix is a level sensor on each tank, pumps that start and stop at set levels, and an alert hours before the rooms run dry.

First, how far does it go?
Ask the next room, and the floor below. If only one room is dry, look at that room: its isolation valve, a blocked mixer or aerator, or its own water heater. If a floor, a building or the whole property is dry, the problem is on the supply side, and the checks below find it.
1. The tank that feeds the rooms
Rooms are fed by gravity from a roof tank, a tank on a stand or a header tank up the hill, or by a booster pump that pressurises the pipes. Look at that tank first. If it's empty, the rooms are only the symptom: the pump that should have filled it didn't.
2. The pump
- Is it running? Listen at the pump room and check the breaker and the motor's overload. A tripped breaker after a power cut is common.
- Running, but the tank isn't rising? The pump may have lost its prime, a valve may be closed, or the foot valve may be blocked.
- Tripping again? Don't keep resetting it. A pump that ran dry can have a damaged seal. Call the electrician or the pump technician.
3. The cistern
Is there water to pump? If the city supply hasn't come for a day or two, the cistern may be at the bottom. Then the choice is a water truck, rationing, or both, and the sooner you know, the more time you have to arrange it.
4. Valves and air
After maintenance, or after a tank has run empty, air can block the pipes even when the tank is full again. Open the highest outlets first to let the air out, and check that every valve someone closed has been opened again.
Why it keeps happening
The same few causes repeat: city water came in the night and nobody started the pumps; the pumps started with the cistern low and ran dry; or a slow leak drained the roof tank before morning. Why Caribbean hotels run out of water goes through each one.
How to stop it
- A level sensor in the tank that feeds the rooms, with an alert at a level that still leaves hours of water. See how to know when a tank is low.
- Pumps that start and stop at set cistern levels, so city water is never missed and the cistern is never drained.
- Dry-run protection, so a pump that loses its water stops before it is damaged. See how to stop a pump running dry.
- A nightly look at the water meter, so a leak is found the morning after it starts. See the night-flow test.
That's what Kanari installs: sensors in your tanks, a switch on your pumps and one message to your team when something needs a person.